About this paper
Yingbo Zhang, Eric Masanet, Shengwei Wang
The authors model single-phase cold-plate cooling across climates, comparing evaporative and dry heat rejection with air cooling. Both liquid options use less cooling energy; evaporative cooling saves 33–56% at settings. Thresholds of 33°C and 49°C achieve at least 99.5% annual free cooling. Warmer coolant can raise GPU power, so total-energy optima vary by climate; these are modeled results, not guarantees.
Summary by alphaXiv.